Product

Projects

Electrical Components for Solar PV, Battery Energy Storage

ESRO3-40 RCBO Residual Current AC Breaker with Overcurrent Protection 1P +N

Product Benefits :

  • Pole No. to 1P +N
  • Rated current to 6-40A
  • Rated voltage to 230/400V~
Download DatasheetRequest A Quote
Category:

Description

The AC Residual Current Circuit breaker is a safety appliance that protects personal safety and prevents electrical fires, can prevent electrical equipment from being damaged. It can be widely used in power distribution systems.

 

Product Benefits :

  • Air circulation
    When two poles are placed adjacent to each other, these channels form a tunnel resulting in effective air circulation around individual poles
  • Bi-connect Termination Possible
    Choice to use Busbar and/or cable in the same terminal,provides reliable termination
  • Din Rail Mounting
    Two step snapping mechanism for easy & efficient mountion in 35mm DIN Rail steadily

 

Technical Data

Mode Electronic / Electromagnetic
Type A / AC /
Tripping curve B C D
Pole No. 1P +N
Rated voltage 230/400V~
Rated frequency 50/60Hz

 

Rated current 6-40A
Rated residual operating current(IΔn) 30.100.300mA
Residual operating current range 0.5 IΔn~IΔn
Rated conditional short-circuit current(lnc) 6000A
Energy limiting class 3
Electrical and Mechanical life 20000

 

Overload Current Protection Characteristics
Test Procedure Type Test Current Initial State Tripping or Non-tripping Time Limit Expected Result Remark
A B.C.D 1.13In Cold t≤1h no tripping
 

B

 

B.C.D

 

1.45In

 

After test A

 

t≤1h

 

tripping

The current steadily rises to the specified

value within 5s

C B.C.D 2.55In Cold 1s<t<60s tripping
 

D

B 3In  

Cold

 

t≤0.1s

 

no tripping

Turn on the auxiliary switch to close the

current

C 5In
D 10In
 

E

B 5In  

Cold

 

t≤0.1s

 

tripping

Turn on the auxiliary switch to close the

current

C 10In
D 20In

 

Residual Current Operating Breaking Time
Type In/A IΔn/A Residual Current(IΔ)Is Corresponding To The Following Breaking Time(S)
AC type Any value Any value In 2In 5In 5A.10A.20A.50A.100A.200A.500A
A type >0.01 1.4In 2.8In 7In
0.3 0.15 0.04 0.04 Max breaking time

 